  1.     SECTION 07723
  2.  
  3.     RIDGE AND SOFFIT VENTS
  4. NOTE ** Cor-A-Vent; high-density polyethylene or polypropylene ridge and soffit vents.
  5. NOTE ** 
  6. NOTE ** This section is based on products manufactured by Cor-A-Vent, Inc., which is located at the following address:
  7. NOTE **    P.O. Box 428
  8. NOTE **    Mishawaka, IN 46546-0428
  9. NOTE **    Attn:  Technical Support Dept.
  10. NOTE **    Tel: (800) 837-8368
  11. NOTE **    Fax: (219) 258-6162
  12. NOTE ** 
  13. NOTE ** Continuous ridge and soffit vents provide balanced ventilation of attic spaces without the use of motors or their consumption of energy, or the maintenance associated with moving parts.  Made of durable corrosion-free high-density polyethylene and polypropylene, Cor-A-Vent profiles are suitable for all common roofing materials and conditions.
  14. NOTE ** 
  15. NOTE ** SECTION 07723 - RIDGE AND SOFFIT VENTS, Copyright 1997, The Architect's Catalog, Inc.
  16.  
  17.  
  18. PART 1  GENERAL
  19.  
  20. 1.1    SECTION INCLUDES
  21. NOTE ** Delete items below not required for project.
  22.  
  23.     A.    Ridge vents.
  24.  
  25.     B.    Soffit vents.
  26.  
  27.     C.    Hip vents.
  28.  
  29. 1.2    RELATED SECTIONS
  30. NOTE ** Delete any sections below not relevant to this project;  add others as required.
  31.  
  32.     A.    Section 06100 - Rough Carpentry.
  33.  
  34.     B.    Section 07310 - Shingles.
  35.  
  36.     C.    Section 07320 - Roof Tiles.
  37.  
  38.     D.    Section 07410 - Metal Roof and Wall Panels.
  39.  
  40. 1.3    SUBMITTALS
  41.  
  42.     A.    Submit under provisions of Section 01300.
  43.  
  44.     B.    Product Data:  Manufacturer's catalog data, standard details, and installation instructions.
  45.  
  46.     C.    Samples:  2 inch (50 mm) long samples of each profile required.
  47.  
  48. 1.4    DELIVERY, STORAGE, AND HANDLING
  49.  
  50.     A.    Store products indoors and protect from construction traffic and damage.
  51.  
  52. PART 2  PRODUCTS
  53.  
  54. 2.1    MANUFACTURER
  55.  
  56.     A.    Manufacturer:  Provide vents fabricated by Cor-A-Vent, Inc.; 2529 Lincolnway West; Mishawaka, IN 46544.  ASD.   Tel: (800) 837-8368. Fax: (800) 645-6162.
  57.  
  58.     B.    Substitutions will not be acceptable.
  59.  
  60. 2.2    MATERIALS
  61.  
  62.     A.    Ridge Vents - General:  Manufactured of corrosion-free, corrugated, laminated, high-density polyethylene (HDPE) or polypropolylene.
  63. NOTE ** Ventilation requirements for attics are generally based on the national Building Codes. They call for a ratio of 1:300, i.e. 1 square foot of ventilation for every 300 square feet of attic area, with 50 percent of the ventilating area at the eaves and 50 percent at the ridge.  Note:  Interpretation of these codes may vary.  For exact information consult your local building code or building official.
  64. NOTE ** 
  65. NOTE ** In a straight gable roof application, a continuous V-400 or V-600 series vent with continuous strip vents at both soffits provides 36 square inches of ventilation per linear foot, which is capable of adequately venting an attic up to 75 feet wide at a ratio of 1:300.  However, buildings 40 feet or wider may require additional soffit venting, depending on local code requirements.  On installations of this size contact the Cor-A-Vent Technical Support Department.
  66. NOTE ** 
  67. NOTE ** Ridge/Soffit vent systems should not be used in conjunction with other roof top vents or gable end vents.
  68. NOTE ** Delete all products below that are not required.  If more than one style of ridge vent is required, insert an identifying name so the contractor will know which type is to be used where.
  69.  
  70.     B.    Ridge Vents:  Cor-A-Vent V-400/V-600 Ridge Vent.
  71.         1.    Net free area:  18 sq in per lin ft (38100 sq mm/m).
  72.         2.    Color:  Black.
  73.         3.    Dimensions:  11 inches (279 mm) wide by 48 inches (1220 mm) long by 1 inch (25 mm) high.
  74.  
  75.     C.    Ridge Vents:  Cor-A-Vent V-600/CS Ridge Vent.
  76.         1.    Net free area:  18 sq in per lin ft (38100 sq mm/m).
  77.         2.    Color:  Black.
  78.         3.    Dimensions:  8-1/2 inches (216 mm) wide by 48 inches (1220 mm) long by 1 inch (25 mm) high.
  79.  
  80.     D.    Ridge Vents:  Cor-A-Vent V-600/T Ridge Vent.
  81.         1.    Net free area:  18 sq in per lin ft (38100 sq mm/m).
  82.         2.    Color:  Black.
  83.         3.    Dimensions:  3-1/2 inches (89 mm) wide by 48 inches (1220 mm) long by 1 inch (25 mm) high.
  84.  
  85.     E.    Ridge Vents:  Cor-A-Vent V-300 Ridge Vent.
  86.         1.    Net free area:  12 sq in per lin ft (25400 sq mm/m).
  87.         2.    Color:  Black.
  88.         3.    Dimensions:  11 inches (279 mm) wide by 48 inches (1200 mm) long by 5/8 inch (16 mm) high.
  89.  
  90.     F.    Ridge Vents:  Cor-A-Vent V-300/CS Ridge Vent.
  91.         1.    Net free area:  12 sq in per lin ft (25400 sq mm/m).
  92.         2.    Color:  Black.
  93.         3.    Dimensions:  8-1/2 inches (216 mm) wide by 48 inches (1220 mm) long by 5/8 inch (16 mm) high.
  94. NOTE ** Soffit vents must always be used with ridge vents to provide balanced attic ventilation and to prevent rain infiltration under severe weather conditions.
  95.  
  96.     G.    Soffit Vents:  Cor-A-Vent S-400 Strip Vent.
  97.         1.    Net free area:  9 sq in per lin ft (19050 sq mm/m).
  98.         2.    Dimensions:  1-1/2 inches (38 mm) wide by 48 inches (1220 mm) long by 1 inch (25 mm) high.
  99. NOTE ** Delete 1 of the following 2 paragraphs.
  100.         3.    Color:  Black.
  101.         4.    Color:  White.
  102.  
  103.     H.    End Caps:  Cor-A-Vent EC-400 End Cap.
  104.         1.    Color:  Black.
  105.         2.    Material:  Aluminum.
  106. NOTE ** The following flashings are used where imbalanced conditions exist to prevent rain infiltration under severe weather conditions.  Consult Cor-A-Vent product literature or call Cor-A-Vent Technical Support Department for assistance for complex roof configurations.
  107. NOTE ** 
  108. NOTE ** Retain 1 or both of the following only when these conditions exist.
  109.  
  110.     I.    Flashing:  Cor-A-Vent WS-400 Solid Weathershield Flashing.
  111.         1.    Color:  Black.
  112.         2.    Material:  Aluminum.
  113.  
  114.     J.    Flashing:  Cor-A-Vent WS-400E Enhanced Weathershield Flashing.
  115.         1.    Color:  Black.
  116.         2.    Material:  Aluminum.
  117.  
  118. PART 3  EXECUTION
  119.  
  120. 3.1    EXAMINATION
  121.  
  122.     A.    Verify that framing, sheathing, and shingles are secured and ready to receive vents.
  123.  
  124.     B.    Verify that there is a 1 inch (25 mm) wide clear air space between sheathing and each side of ridge board or, if trusses are used, a 1-1/2 inch (40 mm) wide continuous clear air space centered on ridge.
  125.  
  126. 3.2    INSTALLATION
  127.  
  128.     A.    General:
  129. NOTE ** Vents should ordinarily be installed at each of the following locations.  Edit as necessary to describe project conditions.  
  130.         1.    Install ridge vents along entire length of roof ridges.
  131.         2.    Install soffit vents along entire length of soffits.
  132.         3.    Install V-300 along entire length of intersection of shed roofs and vertical walls.
  133. NOTE ** Vents along hips are used only when the ridge vents would not provide adequate venting.  Delete the following paragraph if hip vents are unnecessary.
  134.         4.    Install hip vents on hips to provide proper ventilation.
  135.  
  136.     B.    Ridge Vents:
  137.         1.    Fit metal end cap onto one end of the first and last piece of ridge vent.
  138.         2.    Lay a bead of calking on the under side of the end cap, press the piece and cap into position, and nail through the end cap, the ridge vent, and into the roof sheathing.
  139.         3.    Use roofing nails that are long enough to penetrate ridge vent and through roof sheathing.
  140.         4.    Drive the nails down flush so that the vent and end cap are held down firmly.
  141.         5.    Do not indent by over driving.
  142.         6.    Butt each successive piece up snugly, checking for straight alignment.
  143.         7.    Use 2 nails in each end and 1 at each side at center, pulling up slightly when nailing second side to ensure that the vent is nailed at the same pitch as the roof.
  144.         8.    If roof shingles are the heavy dimensional type, a bead of sealant must be applied on top of the shingles to provide weather seal between the shingles and vent.
  145.  
  146.     C.    Cap Shingles:
  147.         1.    Place the first cap shingle with approximately 1/2-inch (40 mm) overhang over the end cap and at each side of the ridge vent.
  148.         2.    Nail down through the shingle, the ridge vent, and through the roof sheathing.
  149.         3.    Nails must be long enough to penetrate the roof sheathing.  In high wind areas, washer-head nails may be used to provide additional holding for the shingle caps.
  150.         4.    Do not fasten V-400 or V-600 vents with staples.
  151.         5.    Preform shingle caps in cold weather to avoid cracking or humping up over the ridge.
  152.         6.    Apply cap shingles with 1 nail each side, up approximately 2-1/2 inches (60 mm) from the overhanging edge.
  153.         7.    Drive nails flush; do not indent.
  154. NOTE ** Delete the following paragraph if project does not have a steep pitch or a wide ridge beam.
  155.  
  156.     D.    Steep Pitch and Wide Ridge Beam Applications:
  157.         1.    Cut ridge vents into 2 half pieces lengthwise.
  158.         2.    Nail half pieces over shingles on either side of the ridge slot.
  159.         3.    Fasten metal flashing over ridge vent.
  160.         4.    Cut oversize shingle ridge caps or lap 12 inch (300 mm) long shingles, and install as specified.
  161. NOTE ** Delete the following paragraph if hip vents are not required.
  162.  
  163.     E.    Hips:  Install ridge vent as needed on hips to provide proper ventilation.  If vent must be run down entire length of hip, do not cut slot within 3 feet (1 m) of the building line.
  164.         1.    Rafters at 24 inches (610 mm) on centers:  Install 8 inch (200 mm) long 2x4 (50 x 100 mm) wood blocking nailed or screwed into hip rafter between each rafter to support roof sheathing.  Nail sheathing to blocking.
  165. NOTE ** Allow 25 percent loss when computing ventilation at hips when blocking is used.
  166.         2.    Apply a continuous bead of sealant to roof shingles immediately prior to placing hip vent to form a seal between roof shingles and bottom of hip vent.
  167.         3.    Vents may be continued down hip without slot to maintain uniform appearance.
  168. NOTE ** Delete the following paragraph if no clerestory or shed roofs are required.
  169.  
  170.     F.    Clerestory and Shed Roofs:  Install continuous vents full length of intersections of roof with vertical walls or clerestories, or at shed roofs in accordance with drawings.
  171. NOTE ** Delete the following paragraph if cedar shakes are not used.
  172.  
  173.     G.    Cedar Shakes:
  174.         1.    Select shakes of uniform thickness to provide an even surface for the vent to rest on.
  175.         2.    Lay a bead of sealant on top of and between edges of shakes to provide weather seal between shakes and vent.
  176.         3.    Install wet sheet on top of vent and cap with shakes. Use nails of sufficient length to penetrate sheathing.
  177. NOTE ** Delete the following paragraph if metal roofs are not used on the project.  Contact Cor-A-Vent for application guide #10 for more information on metal roof applications.
  178.  
  179.     H.    Metal Roofing:  Install ridge and soffit vents as specified by manufacturer and in accordance with drawings.
  180. NOTE ** Delete the following paragraph if tile roofs are not used on the project.  Contact Cor-A-Vent for application guide #9 for more information on tile roof applications.
  181.  
  182.     I.    Tile Roofs:  Install ridge and soffit vents as specified by manufacturer and in accordance with drawings.
  183. NOTE ** Delete the following paragraph if Weathershield flashing is not required by imbalanced venting conditions.
  184.  
  185.     J.    Flashings:  Install specified flashings where indicated on the drawings.
  186.  
  187. 3.3    SOFFIT VENTS
  188.  
  189.     A.    Install continuous vents full length of soffits, unless otherwise indicated.
  190.  
  191.     B.    Ensure that adequate blocking or barriers are installed to prevent insulation from impeding air flow.
  192.  
  193. 3.4    ADJUST AND CLEAN
  194.  